Medium voltage power cables designed for distribution networks and generation units. Suitable for outdoor installations, including direct burial in the ground and placement in underground cable ducts. UV-resistant for enhanced durability.
Conductor: Class 2 Stranded Aluminium, Conductor Screen: Semi-conductive material, Insulation: XLPE (Cross-Linked Polyethylene), Insulation Screen: Semi-conductive material (bonded), Screen: Copper wires and copper tape, Outer Sheath: MDPE (Medium Density Polyethylene) in Red or Black.
Voltage Rating U/Uo: 6/10 (12)kV
Test Voltage: 21kV AC 50Hz (5 mins)
Temp. Rating: -20°C to +60°C
Permissible Conductor Operating Temperature: +90°C
Permissible Short Circuit Temperature up to 5 sec: 250°C
Min. Bend. Radius: 15 x OD
Standards/Approvals:
IEC 60502-2, IEC 60228,
UV Resistant: ISO 4892-3 Abrasion and Tear Resistant: EN 60229-4.1 Impact rated to: AG2 EN 60364-5.51
Medium voltage power cables designed for distribution networks and generation units. Suitable for outdoor installations, including direct burial in the ground and placement in underground cable ducts. UV-resistant for enhanced durability.
Conductor: Class 2 Stranded Aluminium, Conductor Screen: Semi-conductive material, Insulation: XLPE (Cross-Linked Polyethylene), Insulation Screen: Semi-conductive material (bonded), Screen: Copper wires and copper tape, Outer Sheath: MDPE (Medium Density Polyethylene) in Red or Black.
Voltage Rating U/Uo: 6/10 (12)kV
Test Voltage: 21kV AC 50Hz (5 mins)
Temp. Rating: -20°C to +60°C
Permissible Conductor Operating Temperature: +90°C
Permissible Short Circuit Temperature up to 5 sec: 250°C
Min. Bend. Radius: 15 x OD
Standards/Approvals:
IEC 60502-2, IEC 60228,
UV Resistant: ISO 4892-3 Abrasion and Tear Resistant: EN 60229-4.1 Impact rated to: AG2 EN 60364-5.51